- Multistage heating and cooling temperature controllers
- Programmable controllers with standard pre-configured applications
- Programmable via push buttons or a software tool
- Suitable for 1, 2 or 3 compressor units
- Heat/cool or reversing valve output configuration
- Adjustable compressor time delays
- Selectable alarm inputs
- Economizer "Open Air" control for improved comfort and energy savings
- LED indicators for heat/cool
Auxiliary functionsThe second analog input is used for the following functions:
- Standby (on/off)
- Remote setpoint adjustement
- Alarm
- Filter alarm
- Sepoint compensation
- Sensor averaging
- Winter/summer setpoint changeover (analog or digital input)
- Sensor select
- Active sensor
Digital functions
- Day/night changeover
- Standby
- Alarm
- Filter alarm
Свойство
|
Значение
|
Рабочее напряжение
|
AC 24 V
|
Частота
|
50/60 Гц
|
Потребление энергии
|
4 ВА
|
Колич. дискретных входов
|
1
|
Дискретные входы
|
DC 15 V, <10 mA
|
Колич. универсальных входов
|
2
|
Универсальный вход, сигнальный
|
LG-Ni1000 , Pt1000 , DC 0...10 V
|
Колич. дискретных выходов
|
4
|
Дискретные выходы
|
potential-free switching contact , AC 24...230 V, 4(3) A
|
Класс защиты
|
IP20
|
Положение при монтаже
|
Panel mounting
|
Габариты (W x H x D)
|
130 x 106 x 56.5 мм
|